4 | Preparation
Installer reference guide
15
BRP069A61+BRP069A62
Daikin Altherma LAN adapter
4P464229-1E – 2023.11
4.2 Overview of electrical connections
Connectors
X4A
4
N
L
3
2
1
2
1
X1A
X2A
X3A
a1
A
b
c
a2
d
A Smart Grid application only
a1 To solar inverter/energy management system
a2 230VAC detection voltage
b To electricity meter
c To indoor unit (P1/P2)
d To router
Connections
Connection Cable section Wires Maximum cable
length
Accessory cables
Router (X4A) — — 50/100m
(a)
Field-supplied cables
Indoor unit (P1/P2)
(X3A)
0.75~1.25mm
2
2
(b)
200m
Electricity meter
(X2A)
0.75~1.25mm
2
2
(b)
100m
Solar inverter/
energy
management
system + 230VAC
detection voltage
(X1A)
0.75~1.5mm
2
Depends on
application
(c)
100m
(a)
The Ethernet cable delivered as an accessory is 1m long. It is, however, possible to use a
field-supplied Ethernet cable. In this case, respect the maximum allowed distance between
the LAN adapter and the router, which is 50m in case of Cat5e cables, and 100m in case
of Cat6 cables.
(b)
These wires MUST be sheathed. Recommended strip length: 6mm.
(c)
All wiring to X1A MUST be H05VV. Required strip length: 7mm. For more information, see
"4.2.4Solar inverter/energy management system"[418].
4.2.1 Router
Make sure the LAN adapter can be connected via a LAN connection.
The minimum category for the Ethernet cable is Cat5e.
The function of the router in the system depends on the system layout.