9 | Charging refrigerant
Installer reference guide
57
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1B – 2024.05
1 When the unit is powered on and not running, hold down the BS1 pushbutton
for 5 seconds.
Result: You will reach the setting mode, the 7 segment display will show
'200'.
2 Press the BS2 button until you reach page 2–28.
3 When 2–28 is reached, press the BS3 button once.
4 Change the setting to '1' by pressing the BS2 button once.
5 Push the BS3 button once.
6 When the display is not blinking anymore, press the BS3 button again to
activate vacuum mode.
To deactivate vacuum mode:
After charging or vacuuming the unit, please deactivate the vacuum mode by
changing the setting back to '0'.
Make sure to reattach the electronic component box cover and to install the front
cover after the job is finished.
NOTICE
Make sure that all outside panels, except for the service cover on the switch box, are
closed while working.
Close the lid of the switch box firmly before turning on the power.
9.4.3 Charging refrigerant: Setup
See "7.3.3Checking refrigerant piping: Setup"[444].
9.4.4 To completely recharge refrigerant
WARNING
▪ Only use R32 as refrigerant. Other substances may cause explosions and
accidents.
▪ R32 contains fluorinated greenhouse gases. Its global warming potential (GWP)
value is 675. Do NOT vent these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective gloves and safety glasses.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount of
refrigerant.
Prerequisite: Before completely recharging refrigerant, make sure the system is
pumped down, the outdoor unit's external refrigerant piping is checked (leak test,
vacuum drying) and vacuum drying on the outdoor unit's internal refrigerant
piping is performed.
1 If not already done (for vacuum drying of the unit), activate the vacuum mode
(see "9.4.2To activate/deactivate the vacuum mode field setting"[456])
2 Connect the refrigerant cylinder to the service port of the liquid stop valve.
3 Open the liquid stop valve.
4 Charge the complete refrigerant amount.