9 | Charging refrigerant
Installer reference guide
56
AZAS100~140MUV/Y
Sky Air Active-series
4P743509-1B – 2024.05
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is odourless.
9.3 Precautions when charging refrigerant
INFORMATION
Also read the precautions and requirements in the following chapters:
"2General safety precautions"[47]
"7.1Preparing refrigerant piping"[433]
9.4 Completely recharging refrigerant
9.4.1 To determine the complete recharge amount
To determine the complete recharge amount (kg)
Model Length
5~30m
AZAS100-125 2.6kg
AZAS140 2.9kg
9.4.2 To activate/deactivate the vacuum mode field setting
Description
To perform vacuum drying or a complete recharge of the outdoor unit’s internal
refrigerant piping it is necessary to activate the vacuum mode which will open
required valves in the refrigerant circuit so the vacuuming process or recharge of
refrigerant can be done properly.
To activate vacuum mode:
Activating the vacuum mode is done by operating the push buttons BS* on the PCB
(A1P) and reading the feedback from the 7‑segment displays.
Operate the switches and push buttons with an insulated stick (such as a closed
ball-point pen) to avoid touching of live parts.