9 | Electrical installation
Installer reference guide
55
2MXM-A8, 3MXM-A8, 4MXM-A8, 5MXM-A8
R32 Split series
4P766272-5C – 2025.05
Components
Recommended circuit
breaker
3MXM40:16.0A
2MXM68, 3MXM52, 3MXM68, 4MXM68:20A
4MXM80, 5MXM90: 25A
Earth leakage circuit
breaker / residual current
circuit breaker
MUST comply with national wiring regulation
Electrical equipment must comply with EN/IEC 61000-3-12, the European/
International Technical Standard setting the limits for harmonic currents produced
by equipment connected to public low-voltage systems with input current >16 A
and ≤75 A per phase.
9.2 To connect the electrical wiring to the outdoor unit
1 Remove the switch box cover (1 screw).
1
1×
2
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b An excessive strip length may cause electrical shock or leakage
3 Connect the wires between the indoor and outdoor units so that the terminal
numbers match. Make sure to match the symbols for piping and wiring.
4 Make sure to connect correct wiring to correct room.
e-B
e-E
e-C
e-D
a-A
e-A
a-C a-D
a-E
a-B
b c
d
a Terminal for room (A, B, C, D, E)*
b Circuit breaker
c Residual current device
d Power supply wire
e Interconnection wire for room (A, B, C, D, E)*
*May differ depending on the model.