CYP CR-CS4 handleiding

36 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 31 van 36
26
COMMAND
Description and Parameters
set dac N1 N2
Set the voltage level of the specied voltage output.
N1 = 1~16 [Voltage output line]
N2 = 0~100 [Voltage in 0.1V steps]
get dac N1
Show the current voltage level of the specied voltage output line.
N1 = 1~16 [Voltage output line]
set macro N1 N2
Run or stop the specied macro immediately.
N1 = 1~32 [Macro number]
Available values for N2:
RUN [Run the macro]
ABORT [Stop the macro]
set_cond N1 N2
Assign a value to the specied Condition port(s).
N1 = 1~64 [Condition port number]
N2 = 0~255 [Condition value]
Note: Multiple values may be entered for N1 or N2 by separating the
values with commas. Both sets must have the same number of values.
Note: Commands will not be executed unless followed by a carriage return.
Commands are not case-sensitive.