3 — PROGRAMMER MENUS
Curtis 1355 CANopen Soft Starter Module Manual – September 2020
Return to TOC
pg. 12
INTERLOCK MENU (1355-X101 only)
PARAMETER ALLOWABLE RANGE DESCRIPTION
Interlock Type 0 – 1 Selects the interlock type.
0 = Interlock turns on with Digital Input 6.
1 = Interlock turns on with KSI.
Startup Lockout Type 0 – 2 Selects the startup lockout type.
0 = No startup lockout.
1 = KSI-type startup lockout.
To start the motors, KSI must be turned on before a startup request
is received. Controller operation will be disabled immediately if the
startup request is active before KSI is enabled, and a sequence
fault will be declared. If the startup request is received before
interlock switch On but after KSI On, the motor will accelerate to the
requested speed as soon as interlock switch is closed.
2 = Interlock-type startup lockout.
To start the motors, the interlock must be turned on before receiving
a startup request. Controller operation will be disabled immediately if
the startup request is active before the interlock switch is closed, and
a sequence fault will be declared.
Normal operation is restored after a startup lockout by reapplying the startup
request in the correct sequence.
Sequence Delay 0.0 – 5.0 s Sets the PWM output shutoff delay after the interlock switch is turned off.