DALI Lighting Design Guide
16
Doc. 7386H | crestron.com
DALI Loop Wiring
Class I DALI in MC or EMT does not require a shielded wire. When Class II DALI is installed in free air, Crestron
recommends using a shielded cable to minimize induced voltage degradation and interference. DALI wire is sized
appropriately based upon voltage drop due to cable length. Crestron recommends 16 or 18 AWG based upon cable
length. The DALI protocol standard can communicate up to 980 ft (300 m). Per the NEC, class 1 DALI wire may be
run in the same conduit as line voltage wire.