Carrier 39CQ handleiding

58 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 24 van 58
EN - 8
Par Description
Factory setting Setting 1:
Speed from
potentiometer
Setting 2:
Speed from
contact
Setting 3:
Speed on the
keypad
Eur
Level 1 parameters
1 Minimum speed (Hz) 0 20
2 Maximum speed (Hz) 50 0.55 kW motor: 97 , 1.1 kW motor: 60 , 1.4 kW motor: 65
3 Acceleration ramp-up (s / 100 Hz) 5 5
4 Deceleration ramp-down (s / 100 Hz) 10 10
5 Inverter conguration AI.AV AI.AV Pr Pad
6 Nominal motor current (A) Inverter rating
230 V /
: 1 motor: 0.55 kW: 2.4; 1.1 kW: 4.2; 1.4 kW: 5
2 motors: 0.55 kW: 4.8; 1.1 kW: 8.4; 1.4 kW: 10
400 V / Y: 1 motor: 0.55 kW: 1.4; 1.1 kW: 2.4; 1.4 kW: 2.9
2 motors: 0.55 kW: 2.8; 1.1 kW: 4.8; 1.4 kW: 5.8
7 Nominal speed (rpm) 1500 0.55 kW motor: 1390; 1.1 kW motor: 2880; 1.4 kW motor: 2839
8 Nominal motor voltage (V) 230/400 230/400 230/400 230/400
9 Motor output factor (cos φ) 0.85 0.55 kW motor: 0.8; 1.1 kW motor: 0.81; 1.4 kW motor: 0.88
10 Access to the parameters L1 L2
Level 2 parameters
11 On/Off logic selection 0 0
12 Validation of the brake control diS diS
13 Not used
14 Not used
15 Pulse mode reference (Hz) 1.5 1.5
16 Analogue input mode 1 (mA) 4-.20 Volt 4-.20 4-.20
17 Validation of negative preset speeds OFF OFF
18 Preset speed 1 (Hz) 0 Speed 1
19 Preset speed 2 (Hz) 0 Speed 2
20 Preset speed 3 (Hz) 0 Speed 3
21 Preset speed 4 (Hz) 0 Speed 4
22 Load display unit Ld A A A
23 Speed display unit Fr Fr Fr Fr
24 User scale setting 1 1 1 1
25 User security code 0 3-digit code 3-digit code 3-digit code
26 Not used
27 Keypad reference when powering on 0 0 Last 0
28 Copying parameters no No
29 Loading of default settings no No
30 Selection of soft start mode 1 1
31 Selection of stop mode 1 0
32 Dynamic U/f selection OFF ON
33 Flying restart selection 0 2
34 Mode selection (terminal B7) dig Dig
35 Logic output control (terminal B3) n=0 n=0
36 Analogue output control (terminal B1) Fr Fr
37 Maximum switching frequency (kHz) 12-18 12 - 18 (max)
38 Auto calibration 0 0
39 Nominal motor frequency (Hz) 50 50
40 Number of motor poles Auto Auto
41 Voltage mode selection Ur l Ur I
42 Voltage boost at low frequency (%) 3 3
43 Transmission speed by serial link 19.2 19.2
44 Serial link address 1 1
45 Software version
46 Brake opening current threshold (%) 50 50
47 Brake opening current threshold (%) 10 10
48 Brake opening frequency (Hz) 1 1
49 Brake closing frequency (Hz) 2 2
50 Time delay before brake opening (s) 1 1
51 Brake opening time delay (s) 1 1
52 Fieldbus node address 0 0
53 Fieldbus transmission speed 0 0
54 Fieldbus diagnostics 0 0
55 Last switch to safety mode 0 0