4. INSTALLATION
4.1 Mounting on DIN rail and
dimensions
The controller is designed to be mounted on a DIN rail. The  gure below
shows the dimensions for each size.
Mounting:
place the controller on the DIN rail and press it down gently. The tabs at
the back will snap into place and lock the controller.
Removing:
lift the tabs using a screwdriver applied to their release slots. The tabs are
kept in place by springs.
pCO5+
pGNE
pGDx
A
110
45
B
44
156
125
67
18
30
82
151,5
87,7
8,9
133,8
125,7
67,5
33,1
43,9
31,9
151,7
133,8
87,8
23
63,1
54,2
150,8
86,9
133,8
148,3
82,8
RIGHT side
STANDARD 503
RIGHT side for
CHI/DE STANDARD
LEFT side (Ethernet vers.)
STANDARD 503
LEFT side for
CHI/DE STANDARD
57,3
83,5
57,3
83,5
41,9
45,9
to remove for plasterboard installation
to remove for
plasterboard
installation
Fig. 4.a
Dimensions (mm)
Small Medium Buit-in driver Large Extra large
A 227,5 315 315 315 315
B 60 60 60 60 60
B
*
70 70 70 70 70
B ** --75--
Tab. 4.a
*= with USB port/built-in terminal
**= with ULTRACAP module
4.2 Installation
Environmental conditions
Avoid installing the controller and the terminal in places with:
exposure to direct sunlight and to the elements in general;
temperature and humidity outside the product’s range of operation
(see “Technical Speci cations”);
large, rapid  uctuations in room temperature;
strong magnetic and/or radio frequency interference (avoid installing
near transmitting antennas);
strong vibrations or knocks;
presence of explosives or  ammable gas mixtures;
exposure to aggressive and polluting atmospheres (e.g. sulphur and
ammonia vapours, salt mist, fumes) that can cause corrosion and/or
oxidation;
exposure to dust (formation of a corrosive patina with possible
oxidation and reduced insulation);
exposure to water.
Positioning the controller inside the electrical panel
Install the controller inside an electrical panel in a position where it cannot
be reached and is protected from knocks or impacts. The controller should
be placed inside the panel in a position where it is physically separated
from power components (solenoids, contactors, actuators, inverters,
etc.) and their respective cables. The ideal solution is to house these two
circuits in two separate cabinets. Proximity to such devices/cables may
cause random malfunctions that are not immediately evident. The panel’s
casing must allow an adequate  ow of cooling air.
It is recommended to protect the communication cables against
unauthorised access, so as to prevent any "man in the middle" attacks.
Important:
For safety reasons the controller should be installed inside an electrical
panel so that the only accessible parts are the display and the built-in
terminal’s keypad.
Install the controller so that the disconnection devices can be used
safely and without hindrance.
When laying out the wiring, separate as much as possible the probe
cables, digital input cables and serial line cables from the power
cables (connected to contactors, thermomagnetic devices, etc.) avoid
electromagnetic interference.
Never run power cables and probe signal cables in the same conduits
(including the ones in the electrical panels).
For control signals, use shielded cables with twisted wires. If the control
cables have to cross over power cables, the intersections should be as
close as possible to 90 degrees; under no circumstances should the
control cables be laid parallel to the power cables.
Keep the paths of the probe cables as short as possible and avoid
making spiral paths that enclose power devices.
In case of malfunctions do not attempt to repair the device, but
contact a CAREL service centre.
to avoid tampering, it is recommended to place the equipment inside
an electrical panel or locked container. The keys should be kept by
quali ed personnel and their use must be recorded on a speci c
traceability form.