11
ENG
pCO5plus +0300020EN rel. 1.9 - 28.03.2025
1.6 FieldBus port expansion cards
P/N Description Notes
PCO100FD10
(Technical lea et
+050003270)
RS485 serial card
This is used to connect via an electrically isolated interface to an RS485 network. The function implemented
is main (i.e. supervisor), and therefore other secondary controllers or devices can be connected. A maximum
of 64 devices can be connected.
PCO100TLN0
(Technical lea et
+050003270)
tLAN-
Fieldbus card
This is used to connect to devices that communicate via the CAREL proprietary tLAN protocol (2 wires),
to receive information or send commands. Up to  ve devices can be connected, both I/O expansions and
drivers for the management of electronic valves. Alternatively, it can be used to connect the PLD/PST LED
display.
PCO100MPB0
(Technical lea et
+050003270)
Belimo card
This is used to connect the controller to up to 8 servo controls that communicate via the MP-BUS® protocol,
to receive information or send commands.
1.7 Accessories and expansions
P/N Description Notes
PCOS00UC20
(Technical lea et
+0500041IE)
Ultracap
module for c.pCO built-
in driver
This module guarantees temporary power supply to the valve driver only in the event of a power failure, for
su cient time to immediately close the connected electronic valve or valves (one or two). It also avoids the
need to install a solenoid valve in the refrigeration circuit, or a backup battery kit.
EVD0000UC0
(Technical lea et
+0500042IE)
External Ultracap mo-
dule
DIN rail mounted, this can be connected as an alternative to the PCOS00UC20 Ultracap module. It can also
be used in applications with electronic expansion valve drivers not built into the controller (e.g. c.pCO Small -
EVD Evolution - external Ultracap module). If used with c.pCO mini, the module guarantees temporary power
supply to the controller in the event of a power failure, for a su cient time to immediately close the valve
(see technical lea et +0500058IE)
EVD0000E*
(Technical lea et
+050004150)
Electronic expansion
valve driver
The bipolar stepper motor electronic expansion valve driver manages refrigerant expansion in a refrigerant
circuit. The version with RS485 Modbus/Carel serial port is required with the c.PCO controller family. Alterna-
tively, the driver can operate in stand-alone mode.
CPY*
(manuale P/N
+040000030)
CAREL
KUE humidi er
card.
This is used to manage an immersed electrode humidi er and share the main parameters via the Carel /
Modbus RS485 serial line. It features:
all the inputs and outputs needed to completely and autonomously control the humidi er;
three LEDs to indicate: alarms (red), steam production (yellow), 24 Vac power supply (green);
connection to the CPY terminal (P/N CPYTERM*) or to the supervisor network using the Modbus® RTU or
CAREL proprietary protocol.
PCOUMI2000
(Technical lea et
+050003210)
Interface for
OEM series
humidi ers
This is used to control the key parameters of CAREL OEM humidi ers
directly from the c.pCO controller. The values acquired by the sensors (high
level, feed water conductivity, current sensor)
are converted into signals compatible with the inputs available on the controller.
PCOE*
(Technical lea et
+050003265)
pCOe expansion
card
I/O expansion card that o ers users a good combination of inputs and outputs, both digital and analogue.
UXP*
(Technical lea et
+050003271)
pCOe DI expansion
card
I/O expansion card that provides extra digital inputs in a single solution. The expansion features both voltage-
free and fast contact digital inputs.
P+E*
(Technical lea et
+0500059IE)
c.pCOe expansion
card Basic
or Enhanced version
This is used to increase the number of inputs/outputs and relays on the controller.
The Enhanced version has an additional built-in driver for managing a CAREL unipolar electronic expansion
valve.
emeter1/
emeter3
(Technical lea et
+0500046ML/
+0500047ML)
Single-phase/three-
phase energy meter
Single-phase/three-phase energy meter with LCD display for parameter values; especially suitable for measu-
ring active energy and cost allocation. Equipped with RS485 port (Modbus RTU protocol).