Carel iJW handleiding
Handleiding
Je bekijkt pagina 49 van 104

49
ENG
iJW +0300103EN rel. 1.1 - 31.03.2025
Index
Code Description Def Min Max UOM User User terminal
d0 Type of defrost
0 heater by temperature 3 hot gas by time
1 hot gas by temperature 4 heater by time with temperature control
2 heater by time
0 0 4 - S NO
dt1 End defrost temperature (read by Sd) 4/39.2 -50/-58 50/122 °C/°F S YES
dt2 Auxiliary evaporator end defrost temperature (read by Sd2) 4/39.2 -50/-58 50/122 °C/°F S YES
dP1 Maximum defrost duration 45 1 240 min S YES
dP2 Max auxiliary evaporator defrost duration 45 1 240 min S YES
d6 Display on terminals during defrost:
0 = temperature alternating with ‘dEF’; 1 = freeze display; 2 = ‘dEF’.
1 0 2 - S YES
dd Dripping time after defrost (fans off ): 0 = no dripping 2 0 15 min S NO
d7 Skip defrost: 0 = Disabled - 1 = Enabled 0 0 1 - S NO
d8 Bypass high temperature alarm time after defrost 1 1 240 hours S YES
d10 Compressor ON time for running time defrost
0 = function disabled
0 0 240 min S NO
d11 Defrost temperature threshold in running time mode -50/-58 -50/-58 50/122 °C/°F S NO
d15 Start defrost delay 0 0 240 min S NO
dn Nominal defrost duration for skip defrost 75 0 100 % S NO
F2 Evaporator fans with compressor off :
0 = see F0;
1 = always off with compressor off ;
2 = on for anti-stratifi cation;
3 = on for humidity control.
1 0 3 - S NO
F3 Evaporator fans during defrost: 0 = on - 1 = off 1 0 1 - S NO
Fd Post-dripping time after defrost
(fans off with control active)
2 0 15 min S NO
Fpd Evaporator fans during post-dripping
0/1 = On/Off
1 0 1 - S NO
A3 Defrost terminated after maximum time signal:
0 = Disabled 1 = Enabled
0 0 0 - S YES
Below is the trend of the defrost output based on the setting of parameter d0.
300086_054_R01
t
dP1
dt1
Sd
OFF
DEF
d0=4
d0=2
d0=0
DEF
DEF
ON
OFF
ON
OFF
ON
t
t
t
Ref. Description
t time
dt1 End defrost temperature
dP1 Maximum defrost duration
Sd Defrost probe
DEF Defrost
d0 Type of defrost
Fig. 7.r
The heater defrost by time with temperature control (d0=4) activates the defrost output only if the evaporator temperature (Sd)
is less than the value of parameter dt1, and ends after the time defi ned by dP1. This function is useful for energy saving and to
prevent excessive temperatures on the evaporator.
Parameters td1 to td8 can be used to set up to 8 defrost events based on the controller’s clock (RTC), on models where featured.
To set parameters td1 to td8, use the supervisor, the Applica Desktop confi guration software or the Applica app. See “Confi gu-
ration tools”.
Code Description Def. Min Max UOM User User term.
td1..8-d Defrost 1 to 8 - day
0 event disabled 9 Monday to Saturday
1 to 7 Monday to Sunday 10 Saturday & Sunday
8 Monday to Friday 11 every day
0 0 11 - U NO
td1..8-hh Defrost 1 to 8 - hours 0 0 23 hours U NO
td1..8-mm Defrost 1 to 8 - minutes 0 0 59 min U NO
td1..8-time Defrost 1 to 8 - data type for Applica 00:00:00 00:00:00 23:59:59 - U NO
Input and output settings
Code Description Def. Min Max UOM User User term.
/Fb Assign defrost temperature probe (Sd) - see /FA 0 0 7 - S NO
/cb Defrost temperature probe (Sd) calibration 0 -20/ -36 20/ 36 Δ °C/°F S NO
/FF Assign auxiliary evaporator defrost temperature probe (Sd2) - see /FA 0 0 7 - S NO
/cF Auxiliary evaporator defrost temperature probe (Sd2) calibration 0 -20/ -36 20/ 36 Δ° C/°F S NO
DOG Assign defrost digital output - see DOA ... 0 6 - S NO
rOG Defrost digital output logic - see rOA 0 0 1 - S NO
DOH Assign auxiliary evaporator defrost digital output - see DOA ... 0 6 - S NO
rOH Auxiliary evaporator defrost digital output logic - see rOA 0 0 1 - S NO