Defrost (par. DOG)
The relay is activated/deactivated based on the defrost settings (see “Defrost”). Activation/deactivation of the actuator is sig-
nalled by the defrost icon switching on/off on the user terminal (if present).
Auxiliary evaporator defrost (par. DOH)
The relay is activated/deactivated based on the defrost settings (see “Defrost”).
Par. Description Def Min Max UOM User User terminal
DOH Assign auxiliary evaporator defrost digital output - see DOA ... 0 6 - S NO
Evaporator fans (par. DOI)
The relay is activated/deactivated based on the evaporator fan settings (see “Evaporator fans”). Activation/deactivation of the
relay is signalled by the evaporator fan icon switching on/off on the display (if present).
Par. Description Def Min Max UOM User User terminal
DOI Assign evaporator fan digital output - see DOA ... 0 6 - S NO
Dehumidifi cation (par. DOj)
Select the digital output used to manage the dehumidifi cation function. See “Control”.
Par. Description Def Min Max UOM User User terminal
DOj Assign dehumidifi cation heater digital output - see DOA ... 0 6 - S NO
Auxiliary compressor without rotation (par. DOk)
Select the output for the auxiliary compressor without rotation (see “Control”). Setting this output enables an auxiliary compres-
sor that is activated as a second control step, without rotation, i.e. always switching on after the main compressor. In the event
of simultaneous request for both steps, the auxiliary compressor is activated after a delay time set by parameter c11, to avoid
simultaneous starts.
Par. Description Def Min Max UOM User User terminal
DOk Assign auxiliary compressor without rotation digital output - see DOA ... 0 6 - S NO
c11 Second compressor start delay 4 0 250 s S NO
Pump down valve (par. DOn)
Digital output for pump down valve management.
Par. Description Def Min Max UOM User User terminal
DOn Assign pump down valve digital output - see DOA ... 0 6 - S NO
Condensate drain heater (par. DOP)
During defrosting there may be frozen condensate on the bottom of the cabinet that prevents the water thawed from the
evaporator from being drained correctly. The digital output can be confi gured to manage the condensate drain heater function.
The heater is switched on before defrosting (dHA) and remains on after the defrost ends, for the time dHE. The heater can be
activated by selecting a digital output with par. DOP.
Notice: the heater must be protected against overheating (e.g. thermal protector).
Par. Description Def Min Max UOM User User terminal
DOP Assign drain heater digital output - see DOA ... 0 6 - S NO
dHA Condensate drain heater activation time before defrosting 3 1 120 min S No
dHE Condensate drain heater activation time after defrosting 3 1 120 min S No
Anti-sweat heater (par. DOQ)
Select the digital output for demisting the glass (see Anti-sweat heater or fan”).
Par. Description Def Min Max UOM User User terminal
DOQ Assign anti-sweat heater digital output - see DOA ... 0 6 - S NO
Generic function output (par. DOS)
Select the digital output for the generic function with ON/OFF output (see “Generic functions”).
Par. Description Def Min Max UOM User User terminal
DOS Assign generic function digital output- see DOA ... 0 6 - S NO
Evaporator fans (par. DOt)
The relay is activated/deactivated based on the condenser fan settings (see “Condenser fans”).
Par. Description Def Min Max UOM User User terminal
DOt Assign condenser fan digital output - see DOA ... 0 6 - S NO