ENG
iJW +0300103EN rel. 1.1 - 31.03.2025
Index
2.6.2 Large model
C6
NC6
NO6
NO5
NO5
C5
C3
NO3
NO4
NO1
NO2
C1
DI2
GND
S4S2S1
GND
DI1
L
N
100-240 Vac
220 mAarms max
PROBES DI DI
12 34 5 6
N
L
or S3
12 1 2
IEC60730
UL
60730
RELAY
8(3) A
8 A 2FLA
12 LRA
250 Vac
RELAY
8(3) A
8 A 2FLA
12 LRA
250 Vac
RELAY
8(3) A
8 A 2FLA
12 LRA
250 Vac
RELAY
8(3) A
8 A 2FLA
12 LRA
250 Vac
RELAY
20(10) A
16 A 16FLA
96 LRA
250 Vac
RELAY
12(2) A
12 A 5FLA
30 LRA
250 Vac
BXOPZI4850000
SUPERVISORY
SYSTEM
BMS
TTL
Option 01Options:
02-07
shield
+
*
BMS
Tx/Rx
+V
Dir
J4
Fig. 2.l
2.7 Positioning inside the panel
The position of the controller in the electrical cabinet must be chosen so as to guarantee correct physical separation from the
power components (solenoids, contactors, actuators, inverters, ...) and the connected cables. Proximity to such devices/cables
may create random malfunctions that are not immediately evident. The structure of the panel must allow the correct fl ow of
cooling air.
2.8 Electrical installation
Caution: when laying the wiring, "physically" separate the power part from the control part. The proximity of these two sets
of wires will, in most cases, cause problems of induced disturbance or, over time, malfunctions or damage to the components.
The ideal solution is to house these two circuits in two separate cabinets. Sometimes this is not possible, and therefore the pow-
er part and the control part must be installed in two separate areas inside the same panel.
For the control signals, it is recommended to use shielded cables with twisted wires. If the control cables have to cross over the
power cables, the intersections must be as near as possible to 90 degrees, always avoiding running the control cables parallel
to the power cables.
Pay attention to the following warnings:
• use cable ends suitable for the corresponding terminals. Loosen each screw and insert the cable ends, then tighten the
screws. When the operation is completed, slightly tug the cables to check they are suffi ciently tight;
• Separate as much as possible the probe signal, digital input and serial line cables from the cables carrying inductive loads and
power cables to avoid possible electromagnetic disturbance. Never run power cables (including the electrical cables) and
probe signal cables in the same conduits. Do not install the probe cables in the immediate vicinity of power devices (contac-
tors, circuit breakers or similar);
• Reduce the path of the probe cables as much as possible, and avoid spiral paths that enclose power devices;
• Avoid touching or nearly touching the electronic components fi tted on the boards to avoid electrostatic discharges (extreme-
ly damaging) from the operator to the components;
• Do not secure the cables to the terminals by pressing the screwdriver with excessive force, to avoid damaging the controller:
maximum tightening torque: 0.22-0.25 N•m.
• For applications subject to considerable vibrations (1.5 mm pk-pk 10/55 Hz), secure the cables connected to the controller
around 3 cm from the connectors using cable ties;
• All the extra low voltage connections (analogue and digital inputs, analogue outputs, serial bus connections, power supplies)
must have reinforced or double insulation from the mains network.