Hecu +0300023EN rel. 1.2 - 14.12.2021
Troubleshooting Delay Reset Notes
- Check evaporator confi guration on screen Eab00 and following Hecu side (number of
evaporators, size, type of control installed,..)
- Check FBus connection (connections, wiring, polarity,...)
- MPXPRO / UC status (check control side confi guration, serial address H0 parameter, if
necessary re-confi gure fi rst)
No serious
alarm
- Check evaporator confi guration on screen Eab00 and following Hecu side (number of
evaporators, size, type of control installed,..)
- Check FBus connection (connections, wiring, polarity,...)
- MPXPRO / UC status (check control side confi guration, serial address H0 parameter, if
necessary re-confi gure fi rst)
No serious
alarm
- Check parameter P1 (it must be set to 2) on MPXPRO with respect to the valve installed
in the evaporator (must be Carel E2V electronic valve).
- Check correct level switches operation in the receiver
- Assess the correct amount of oil in the equipment and the oil return from the evapo-
rators
Settable on screen Fab26
- Check that the DIs associated with this function have been confi gured correctly
Tab. 8.c