54
Hecu +0300023EN rel. 1.2 - 14.12.2021
Screen
index
Enable screen Description Serious
alarm
Normal
alarm
Action Description
ALW74 MPX_3_Alm_MOP Store 3: MOP alarm x
ALW75 MPX_3_Alm_LOP Store 3: LOP alarm x
ALW76 MPX_3_Alm_Edc Store 3: stepper driver communi-
cation error
x
ALW77 MPX_3_Alm_EFS Store 3: Stepper motor error x
ALW78 MPX_3_Alm_bLO Store 3: Installation or confi g
problems on EEV driver
x
ALW79 al_Mpx4_Offl ine Store 4 offl ine x / Evaporator 4 confi gured by Hecu but
MPXPRO / UC device not connected via
Fieldbus or offl ine
ALW80 MPX_4_Alm_LTD Store 4: Low temperature alarm
[air off ]
x
ALW81 MPX_4_Alm_HTD Store 4: High temperature alarm
[air off ]
x
ALW82 MPX_4_Alm_LTS Store 4: Low temperature alarm
[air on]
x
ALW83 MPX_4_Alm_HTS Store 4: High temperature alarm
[air on]
x
ALW84 MPX_4_Alm_Defrost_Timeout Store 4: Defrost timeout x
ALW85 MPX_4_Alm_LSH Store 4: Low superheat alarm x
ALW86 MPX_4_Alm_LSA Store 4: Low suction temperature
alarm
x
ALW87 MPX_4_Alm_MOP Store 4: MOP alarm x
ALW88 MPX_4_Alm_LOP Store 4: LOP alarm x
ALW89 MPX_4_Alm_Edc Store 4: stepper driver communi-
cation error
x
ALW90 MPX_4_Alm_EFS Store 4: Stepper motor error x
ALW91 MPX_4_Alm_bLO Store 4: Installation or confi g
problems on EEV driver
x
ALW92 al_Mpx5_Offl ine Store 5 offl ine x / Evaporator 5 confi gured by Hecu but
MPXPRO / UC device not connected via
Fieldbus or offl ine
ALW93 MPX_5_Alm_LTD Store 5: Low temperature alarm
[air off ]
x
ALW94 MPX_5_Alm_HTD Store 5: High temperature alarm
[air off ]
x
ALW95 MPX_5_Alm_LTS Store 5: Low temperature alarm
[air on]
x
ALW96 MPX_5_Alm_HTS Store 5: High temperature alarm
[air on]
x
ALW97 MPX_5_Alm_Defrost_Timeout Store 5: Defrost timeout x
ALW98 MPX_5_Alm_LSH Store 5: Low superheat alarm x
ALW99 MPX_5_Alm_LSA Store 5: Low suction temperature
alarm
x
ALZ00 MPX_5_Alm_MOP Store 5: MOP alarm x
ALZ01 MPX_5_Alm_LOP Store 5: LOP alarm x
ALZ02 MPX_5_Alm_Edc Store 5: stepper driver communi-
cation error
x
ALZ03 MPX_5_Alm_EFS Store 5: Stepper motor error x
ALZ04 MPX_5_Alm_bLO Store 5: Installation or confi g
problems on EEV driver
x
ALZ06 Al_OR_Mpx1_Liquid Liquid return from MPX offl ine
during fl ush
x
Al_Mpx1_Liquid Alarm MPX1 x
Al_Mpx2Liquid Alarm MPX2 x
Al_Mpx3_Liquid Alarm MPX3 x
Al_Mpx4_Liquid Alarm MPX4 x
Al_Mpx5_Liquid Alarm MPX5 x
ALZ08 Al_OR_Mpx_Valve Carel EXV valve not confi gured
in MPX PRO
The unit will switch off in 10
hours
x Unit shutdown in 10 hours Valve managed by MPXPRO / UC is not
electronic Carel E2V (only one possible with
Hecu)
If P1=1 is set (Carel E2V electronic valve)
and a PWM valve is physically present in
the evaporator, an EoC error appears on
MPXPRO
ALP09 Al_SCI_LowOilLev SCI compressor low oil level
alarm
x Compressor shutdown Function to be activated on screen Fab26.
If the low oil level DI is activated, the control
is interrupted.
ALP10 Al_SCI_OilMng_DI_NotCfg SCI oil managements.
One or more inputs are not
confi gured
x / SCI Sensor Oil management enabled in
screen Fab26.
Associated DI are not confi gured in screen
Faa61 (Level 1) and Faa62 (Level 2)
SCI_OilLev1_Pres Oil level 1 x
SCI_OilLev2_Pres Oil level 2 x