Hecu +0300023EN rel. 1.2 - 14.12.2021
Inputs
STO (safe torque off )
Voltage-free contact input, reinforced insulation (24 V SELV circuit):
open contact voltage: <24 V
closed contact current: 40 mA typical
max. cable length 25 m
Data
connection
interface
Serial data connection
RS485, Modbus® protocol, maximum baud rate 19200 bit/s
Typical reception resistance 96 KΩ, equal to 1/8 of unit load, i.e. 1/256 of maximum load applicable on
the line
Insulation Reinforced (24 V SELV circuit)
Maximum length 100 m shielded cable
Other
Ingress protection IP00
Ball pressure test temperature 125°C
Construction Device to be incorporated
Type of automatic action PS2********0* and PS2********S* models: Type 1 (functional control)
PS2********1* and PS2********P* models: Type 2 (safety control)
Pulse voltage 4 kV (overvoltage category III)
Standards
compliance
CE
Low voltage directive
2014/35/EU
IEC 60730-1, IEC 60335-1 (sections 29 and 30), IEC 60335-2-34 (sections 19.101 and 19.103)
Electromagnetic com-
patibility directive
2014/30/EU
EN 61800-3, ed.2.0: Adjustable speed electrical power drive systems. EMC requirements, including
specifi c test methods.
EN61000-3-2: Electromagnetic compatibility (EMC) Part 3-2: Limits - Limits for harmonic current emis-
sions (equipment input current <= 16 A per phase).
EN61000-3-12: Electromagnetic compatibility (EMC) Part 3-12: Limits - Limits for harmonic current emis-
sions (equipment input current > 16 A and <=75 A per phase).
UL UL 60730-1, UL 60335-1 (sections 29 and 30), UL 60335-2-34 (sections 19.101 and 19.103). See chap. "UL requirements for installation".
Tab. 2.e
Network address
The confi guration and programming of the Power+ drive, as well as the
run/stop commands and speed reference, are managed by a CAREL pCO
controller or by any BMS (Building Management System) via RS485 serial
connection with Modbus® protocol. The ModBus® network address can
be set from 1 to 246, and this number comprises the basic address set by
parameter, and the address set by the 4 dipswitches inside the drive, from
0 to 15. By changing the basic address, it is possible to cover the entire
range of addresses.
Mod. add. Description Def Min Max UOM R/W
32 Basic address 1 1 232 - R/W
120 Network address - 1 246 - R
121 Dipswitch address - 0 15 - R
Tab. 2.f
Caution:
Changes to the device’s serial address, either using the dipswitches or
the parameter, are eff ective only when the device is next switched on
or reset.
The confi guration of the address set manually by the dipswitches on the
drive is shown below.
1
ON
OFF
234
Fig. 2.k
Caution: before accessing the dipswitches, power off and wait for
the LEDs to go off .
Dipswitch address
Dipswitches
Dipswitch
address
1234
OFF OFF OFF OFF 0
ON OFF OFF OFF 1
OFF ON OFF OFF 2
………… …
ON ON ON ON 15
Tab. 2.g
Warning: if the address set by the dipswitches is between 0 and 14,
the network address is the sum of the basic address and the dipswitch
address, while baud rate and parity are set by the corresponding
parameters.
If the dipswitch address is set to 15, communication mode is set to:
• 19200 bit/s; no parity; 2 stop bits; network address 1
regardless of the value of the corresponding parameters.
It is recommended to avoid setting the dipswitch address to 15 as a
normal confi guration.