INSTALLATION
Installation is fast and simple. A sturdy framed wall opening should be prepared in advance to the size indicated for your
fan in the charts above. With lag bolts for wooden frames or nut, bolt and lock washers for steel frames, secure the fan
using the four mounting holes provided, one in each corner of the fan.
ELECTRICAL CONNECTIONS
WARNING: BE SURE POWER IS OFF AT THE ELECTRICAL PANEL BEFORE WIRING.
WARNING: ALL ELECTRICAL WORK SHOULD BE PERFORMED BY A QUALIFIED ELECTRICIAN.
These fans are supplied with single, two or variable speed motors. Single and two speed motors are 120V only. Variable speed motors are dual volt-
age. All dual voltage motors are pre-wired at 240V in our factory. Rewire motor as per motor nameplate if running fan at 120V. Please see the motor
nameplate for wiring diagram. Make electrical connections in motor connection box as per the motor nameplate. Follow Chart #1 for wire sizes. Two
speed fans require a two speed control or 3 position toggle switch to change from high/low/off. See wiring diagram with control for 2 speed wiring
instructions.
AX & P_EXHAUST FANS_M_M0111 - 03/04/23 Page 3 of 4
AX & P SERIES EXHAUST FANS
Explosion proof fans are equipped with single speed explosion proof motors and aluminum blades so sparks cannot occur if a metal object
obstructs the blade path. Explosion proof fans have the same quality housing panel and heavy gauge welded guard as the AX & P Fans. These
fans should be used to ventilate hazardous areas. Locations are considered hazardous if the atmosphere contains or may contain gas, vapor, or
dust in explosive quantities.
Canarm explosion proof fans DO meet the following hazardous
classifications.
Canarm explosion proof fans DO NOT meet the following hazardous
classifications.
CLASS 1, DIVISION 1 (GASES, VAPORS)
GROUP C Acetaldehyde, cyclopropane, diethlether,
Ethylene, isoprene
GROUP D Acetone, acrylonitrile, ammonia, benzene, butane,
ethylene dichloride, gasoline, hexane, methane,
methanol, naphtha, propane, propylene styrene,
toluene, vinyl, acetate, vinyl chloride, xylene
CLASS 2, DIVISION 1 (COMBUSTIBLE DUSTS)
GROUP F Carbon black, coke or coal dust
GROUP G Flour, starch or graindust
CLASS 1, DIVISION 1 (GASES, VAPORS)
GROUP A Acetylene
GROUP B Butadiene, ethylene oxide, hydrogen, propylene oxide
CLASS 2, DIVISION 1 (COMBUSTIBLE DUSTS)
GROUP E Aluminum, magnesium and other metal dusts
with similar characteristics
200V 230V 460V 200V 230V 460V 200V 230V 460V
1/8 14(18)* 14(18)* 14(18)* 14(18)* 14(18)* 14(18)* 14(16)* 14(16)* 14(18)*
1/6 14(18)* 14(18)* 14(18)* 14(18)* 14(18)* 14(18)* 14 14(16)* 14(18)*
1/4 14(18)* 14(18)* 14(18)* 14(16)* 14(18)* 14(18)* 14 14 14(18)*
1/3 14(18)* 14(18)* 14(18)* 14(16)* 14(16)* 14(18)* 12 14 14(18)*
1/2 14(16)* 14(18)* 14(18)* 12 14(16)* 14(18)* 10 12 14(18)*
3/4 14(16)* 14(16)* 14(18)* 12 14 14(18)* 10 10 14(16)*
1 14 14(16)* 14(18)* 12 12 14(18)* 8 10 14(16)*
1 1/2 12 14 14(18)* 10 10 14(16)* 6 8 14
2 12 12 14(18)* 8 10 14(16)* 6 6 12
3 10 12 14(18)* 6 8 14 4 6 12
25 to 50 Feet 100 Feet 150 to 200 Feet
Motor HP
THE MOTOR AMBIENT TEMPERATURE IS NOT TO EXCEED +40˚C OR -25˚C UNLESS THE MOTOR NAMEPLATE SPECIFICALLY PERMITS
ANOTHER VALUE. THE FOLLOWING TABLE INDICATES WHICH HAZARDOUS CLASSIFICATIONS CANARM EXPLOSION PROOF FANS DO
AND DO NOT MEET.
CHART#1
Table A Minimum Wire Sizes for Three-Phase Motors