cnReach N500 User Guide System Configuration
phn-4980_001v004 August 2019)
2-63
Each Device is set up with its connection parameters, and optional error indicators. Under each device a
series of polls is defined, blocks of Modbus registers to fetch. Polls also have optional error indicators.
Under each poll the particular values that are of interest are defined.One to many devices can be
configured, each with their particular parameters. If you need ModbusRTU, configure the Data
Concentrator to use the Modbus Bridge.
The error registers can be set to -1 to disable, or to any valid Modbus register (0-65534). If there’s a
conflict between error registers and output values, the error register will be written briefly, then the
output value. Errors on any Poll under this device will set (1) the error registers, and only if all Polls are
successful will the error registers be cleared (0).