12
VD0028
ExhaUst hood
intakE hood
tapE and dUCt tiE
b
optional dUCt
loCation
3.7 inSTAlling TWO ExTERiOR HOOdS
3. INSTALLATION (Contd)
WARNING
VQ0010
!
!
Make sure intake hood is located at least 10 feet away from any of the following:
Dryer exhaust, central vacuum vent
Gas meter exhaust, gas barbecue-grill
Any exhaust vents or chimney from a combustion source
Garbage bin and any other source of contamination such as parking lots, streets
For multifamily buildings only:
Make sure exhaust hood is located at least 3 feet away from any of the following:
Property lines
Operable openings into buildings (door, window)
Intake and exhaust hood(s) shall be protected with corrosion-resistant screens,
louvers or grilles having openings not less than
1/4 inch and not larger than 1/2 inch.
Install hood(s) at least at 18 inches away from the ground OR depth of expected
snow accumulation, whichever is greater.
To minimize cross-contamination of exhausted stale air into the fresh air intake:
Single detached, attached homes and townhouses:
Maintain a 6 feet minimum separation distance between outdoor air intake and
exhaust hoods OR use an approved factory-built intake/exhaust combination
termination fitting.
Multifamily buildings:
Maintain a 10 feet minimum separation distance between outdoor air intake and
exhaust hoods OR use an approved factory-built intake/exhaust combination
termination fitting.
Ignoring these recommendations could significantly degrade the quality of the
incoming air which, in some cases, could result in health consequences. In the
event of a conflict between our recommendations and any local requirements, the
latter shall have priority.
3.8 COnnECTing THE dRAin
CAUTION
A drain tubing (included) must be installed for all HRV units. For ERV units, it is not required, however, it is
recommended for climates where the outdoor temperature typically remains below -13°F, (over a 24-hour period)
for several days in a row, combined with an indoor humidity of 40% or higher.
VO0273A
16"
(406 mm)
16"
(406 mm)
Cut 2 sections of the plastic tube, at least 16” long, and attach them
to each inner drain fitting, located under the unit.
Join both short sections to the “T” junction and main tube as shown.
VD0387
drain plUg loCations
NOTE: For ERV units installed in cold climate, remove both drain
plugs inside the unit prior to install tubing.
VD0337A
± 1”
TIE WRAP
Make a water trap loop in the tube to prevent the unit from
drawing unpleasant odors from the drain source. Make sure this
loop is located OVER the “T” as shown. Run the tube to the floor
drain or to an alternative drain pipe or pail.
iMportant
If using a pail to collect water, locate the tube end approximately
1” from the top of the pail in order to prevent water from being
drawn back up into the unit.
a
b
b
a
CaUlking
CaUlking
Legend:
A - Single family ≥ 6 ft
Multifamily ≥ 10 ft
B - 18" or depth of expected snow accumulation
Refer to figure above for connecting insulated
ducts to the exterior hoods. An Anti-gust intake
hood’ should be installed in regions where a lot of
snow is expected to fall.