3.2 CONNECTING THE INSULATED DUCTS TO THE UNIT
1. Slide the inner 6 in. round flexible duct over the port and tie it using a tie-wrap.
2. Pull the insulation over the inner ring of the port without compressing it to minimize possible condensation
buildup within the duct, as well as minimize building heat loss and gain.
3. Use duct tape to seal the outer membrane of the insulated duct to the outer ring of the port to create
an air-tight path and to minimize building heat loss and gain and reduce the potential for condensation.
šŸ’” Avoid blocking the test ports with the duct tape.
CAUTION
Make sure to replace insulation around any openings made in the building envelope
when installing unit or ducting. Seal insulation with tape or caulk to minimize building
heat loss and gain and to reduce the potential for condensation.
⚠WARNING
Make sure the outdoor intake hood is at least 12 inches above the ground and 6 feet away
from any of the following: Dryer exhaust, high-efficiency furnace vent, central vacuum
vent, gas meter exhaust, gas barbecue-grill, any exhaust from a combustion source,
garbage bin and any other source of contamination.
šŸ’” Make sure that the outdoor intake hood is easily accessible for annual maintenance. If located above the
first floor, place it close to a window or balcony to allow ease of access.
IMPORTANT - The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for best
performance, and avoid installing the fan with smaller ducts than recommended. Insulation around the
ducts can reduce energy loss and inhibit mold growth. Fans installed with existing ducts may not achieve
their rated airflow.
3.3 CONNECT POWER
3.3.1 FIN-180P
Plug the unit power cord into a mating 3-prong grounding receptacle.
3.3.2 FIN-180P-HW
⚠WARNING
Risk of electric shock. Electrical wiring must be done by qualified personnel in accordance with
all applicable codes and standards. Before connecting wires, switch power off at service panel
and lock service disconnecting means to prevent power from being switched on accidentally.
NOTE: The insulated duct and the low voltage
wires not shown to simplify the illustration.
1. Detach the electrical compartment cover from
the unit by removing its retaining screw.
2. Install the included wire clamp on the unit.
Insert the house wiring cable through the wire
clamp and tighten the wire clamp to secure
the cable.
3. Using provided wire connectors, connect
wires as follows: BLACK to BLACK, WHITE
to WHITE and GREEN or BARE wire under
ground screw. DO NOT FORGET TO
CONNECT THE GROUND.
4. Put back in place the electrical compartment
cover, taking care not to pinch wires. Restore
power to the unit.
VE0424
Ground screw
Hole for low voltage wires only
(wires not shown)
VJ0151
Test ports