2. INSTALLATION (Contd)
2.5 planning oF THe ducTWork
Keep it simple. Plan for a minimum of bends and joints.
Keep the length of insulated ducts to a minimum.
Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would
cause clogging of the filters and recovery module.
If the house has two floors or more, be sure to plan for at least one exhaust register on the highest lived-in level.
2.6 insTalling THe ducTWork and regisTers
2.6.1 Fully ducTed sysTem (as illusTraTed in secTions 1.1.1 and 1.2.1)
Stale air exhaust ductwork:
Install the stale air exhaust registers where the contaminants are produced: kitchen, living room, etc. Position the registers as far
from the stairway as possible and in such a way that the air circulates in all the lived-in spaces in the house.
If a register is installed in the kitchen, it must be located at least 4 feet from the range.
Install the registers 6 to 12 inches from the ceiling on an interior wall OR install them in the ceiling.
Fresh air distribution ductwork:
Install the fresh air distribution registers in bedrooms, dining rooms, living room and basement.
Keep in mind that the fresh air registers must be located as far as possible from the stale air registers.
Install the registers in the ceiling OR 6 to 12 inches from the ceiling on an interior wall.
If a register must be floor installed, direct the airflow up the wall.
WARNING
Never install a stale air exhaust register in a closed room where a combustion device operates, such as a gas furnace,
a gas water heater or a fireplace.
!