SAFETY & IMPORTANT INFORMATION
Warning
EXPLANATION OF SYMBOLS DISPLAYED ON THE UNIT
WARNING Risk of fire / flammable material. If the refrigerant is leaked, together
with an external ignition source, there is a possibility of ignition.
Read the OPERATING INSTRUCTIONS carefully before operation.
Service personnel are required to carefully read the OPERATING INSTRUCTIONS and
INSTALLATION MANUAL before operation.
1.
Transport of equipment containing flammable refrigerants
See transport regulations.
2.
Marking of equipment using signs
See local regulations.
3.
Disposal of equipment using flammable refrigerants
See national regulations.
4. Storage of equipment/appliances
The storage of equipment should be in accordance with the manufacturer's instructions.
5.
Storage of packed (unsold) equipment
Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the
refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations
•
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces
shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of
flammable material.
6.
Information on servicing
1)
Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of
ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
2)
Work procedure
Work shall be undertaken under a controlled procedure to minimize the risk of a flammable gas or vapor being present while the work is being performed.
3)
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be
avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of
flammable material.
4)
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable
atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e., non-sparking, adequately sealed or
intrinsically safe.
5)
Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to
hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area
Page 6