VIII. SERVICE
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power
whenever servicing unit. More than one disconnect may
be required to de-energize unit.
Any service performed on the ARCHITECTURAL Recessed Series
air curtain MUST be done by qualied personnel.
Berner air curtains require very little servicing. All parts are
easily accessible for periodic inspection and maintenance.
Units should be cleaned at least twice a year. Your particular
application (the amount of dirt and dust in the air) and location
of the unit(s) will determine how often your unit(s) will need to
be cleaned and serviced. All motors have permanently lubricated,
sealed, sleeve bearings and require no maintenance.
A. To remove the blower module and clean or replace the fans
and motor:
1. Disconnect and lockout power to the unit.
2. Remove the bottom access cover by removing (4) Phil-
lips head machine screws located at the covers corners.
See Figure 7.
3. If desired, the nozzle surround may be removed to
provide more working room. To remove the nozzle
surround, remove the (4) Phillips head machine screws
from the corners. The Intelliswitch® ribbon cable must
also be disconnected from the back of the display circuit
board before the nozzle surround can be set aside.
4. Disconnect motor power wires/harness from motor.
5. If the unit has electric heat, the heaters need to be
disconnected from supply wiring. Each fan housing will
have a heating element on both of its sides, spanning
the inlet venturi. Each heating element will have (2) ¼”
quick disconnects for power supply wiring. In addition,
the heating elements located on the inside of the mod-
ule will have (2) ¼” quick disconnects for the auto reset
thermal cutouts. Label and separate all of those connec-
tions. See Figure 8.
6. Using a 5/16” hex driver, loosen and remove the (4) self
drilling screws that hold the blower plate to the frame of
the unit. Remove the two screws at the top of the prod-
uct last, as after they are removed, the module will be
free to drop out of the cabinet. See Figure 9 for location
of all screws.
7. Wearing protective gloves, hold the module by the mo-
tor, and rotate the module top forward and drop it down
through the bottom of the unit. See Figure10.
8. To remove the fans and/or motor, loosen the set screws
in the fan wheel hubs by using a 5/32” Allen wrench that
is at least 152.4mm long. The set screw can be accessed
up through the fans discharge.
9. Next, remove the two blower housings by removing the
(8) screws that attach the fan housings to the blower
plate. When the fan housings are free, slide them and
their fan wheels o to each side.
10. Remove the motor clips from the motor mounts, discon-
nect the motor ground wire if necessary, and lift the
motor up and out of its cradle.
11. Reinstall in reverse order of removal.