VIII. MAINTENANCE & CLEANING
CAUTION: ELECTRIC SHOCK HAZARD Disconnect power
whenever servicing unit. More than one disconnect may be
required to de-energize unit.
Keep your air curtain operating at peak eciency by cleaning
the blower wheels, motor(s) and intake grille. Buildup of dust
on the blower wheels can cause vibration, noise and excessive
wear on the motor bearings. The frequency of cleaning will
depend on the environment where the unit is operating.
Dirty, dusty or greasy environments could require a cleaning
schedule of once every two months. Otherwise, the unit(s)
should be scheduled for cleaning a minimum of once every (6)
months. To access the interior of the unit:
A. Disconnect and lockout power to the unit. If necessary
remove the blower assembly. See Section VIII SERVICE for
instructions on how to remove blower module.
B. Remove the bottom access cover by removing (2) Phillips
head machine screws located at the covers corners.
See Figure 7.
C. Vacuum and scrape (if necessary) to remove the buildup
of dirt and debris from the interior of the air curtain. The
motor(s) are permanently lubricated and require no ad-
ditional lubrication.
D. Pull the lter out from underneath the struts of the bottom
access cover. It is easiest to work from the middle, pull-
ing one side out and then the other. Spray the lter with
warm, soapy water, rinse, and pat dry.
E. Replace Filter.
F. Reinstall the bottom access cover.
G. Switch the power on after cleaning.
CAUTION: STAND CLEAR of the unit or wear safety goggles
as loose debris may be present and may exit the nozzle.
VII. MAINTENANCE & CLEANING
Figure 7
Figure 6 - Air Stream Adjustment
B. AIR STREAM ADJUSTMENT
1. With the air curtain operating and the door in its full
open position, check to see that nothing is obstructing
the airow at the discharge nozzle vanes.
2. Find the air stream split location. Hold a handkerchief
by its corners, approximately 304mm above the oor.
Gently move the handkerchief back and forth in the
doorway. Make sure the air is being directed to both the
inside and the outside. See Figure 6. The split location
is indicated where the handkerchief is vertical with
minimal or no uttering.
3. The split location should be approximately 76mm
outside the doorway. If necessary adjust the discharge
nozzle vanes by de-energizing the unit, loosening the
nozzle vane locking screws and adjusting vanes.
AIR
InteriorExterior
304.8mm
AIR
76.2mm