INDOOR MOUNTING ONLY
To achieve optimum protection, the air curtain should be
mounted on the inside of the building, ush to the wall and
as close to the top of the door opening as possible. To ensure
peak performance, keep the air stream free of obstructions.
The air curtain will not perform properly if negative air
pressure exists in the building. Under these conditions,
a means for makeup air to the building must be provided
so that the air pressure on both sides of the opening is in
balance.
Before mounting the air curtain, check the supporting structure
to verify that it has sucient load-carrying capacity to support
the weight of the air curtain(s). The mounting hardware
(supplied by others) should be capable of supporting a
minimum of three (3) times the weight of the air curtain.
See Table 1.
A. When determining the mounting location for the unit(s),
make sure that nothing interferes with the curtain of air
developed when the discharge vanes are directed from 0°
to 20° toward the door opening. If the air stream strikes any
obstruction (the top edge of the doorway, a door opening
device, etc.), the eectiveness of the unit will be greatly
reduced. See Figure 2.
B. For optimum performance, the bottom of the discharge
nozzle should be located in such a manner that it is spaced
out from the wall 10mm for every 25mm the unit is above
the door opening.
C. Do not block (obstruct) the air intake screen. Insucient
airow can cause the unit to overheat.
D. Electric heated unit(s) shall:
1. Have a minimum clearance of at least 305mm between
the bottom of the unit and the oor.
2. Be installed Indoors Only.
E. The unit is shipped without the front and back trim in-
stalled to protect it from shipping damage. This trim need
not be installed until after the unit is hung. See Figure 3.
TABLE 1 - Weight Charts
Figure 2 - General Mounting
II. MOUNTING PREPARATION
Model
TOTAL NET WEIGHT (kgs.)
Ambient Electric Heat
Steam/Hot
Water Heat
ARE12-1036 46 48 57
ARE12-1042 49 51 62
ARE12-1048 52 54 66
ARE12-1060 61 63 80
ARE12-2060 78 81 97
ARE12-2072 82 86 104
ARE12-2078 85 89 108
ARE12-2084 88 92 112
ARE12-2096 93 97 120
ARE12-3096 111 116 138
ARE12-3108 124 129 153
ARE12-3120 129 135 161
ARE12-3132 135 140 171
ARE12-3144 140 145 178
ARE12-4144 165 172 203
Model
TOTAL NET WEIGHT (kgs)
Ambient Electric Heat
Steam/Hot
Water Heat
ARE16-1036 47 49 59
ARE16-1042 50 52 68
ARE16-1048 53 55 73
ARE16-1060 62 64 85
ARE16-2060 80 84 103
ARE16-2072 85 89 110
ARE16-2078 88 92 115
ARE16-2084 91 94 119
ARE16-2096 96 99 126
ARE16-3096 115 120 146
ARE16-3108 127 133 160
ARE16-3120 133 139 168
ARE16-3132 138 144 178
ARE16-3144 143 149 185
ARE16-4144 170 177 212
1.83m minimum*
20°
0" minimum
AIR
Discharge
Nozzle
0" minimum
side clearance
from combustible
material
A
I
R
A
I
R
*Electrically Heated Units Only
INTERIOR
EXTERIOR