AP-S15HRIP / AP-S15IP / AP-S158IP
Owner’s Manual
– 24 –
AtlasIED.com
TELEPHONE: (800) 876-3333
SUPPORT@ATLASIED.COM
1601 JACK MCKAY BLVD.
ENNIS, TEXAS 75119 U.S.A.
6. Humidity Alarm Settings
Enter the value for the humidity alarm to trigger. The operating range is 15-95%
Select Save.
If the alarms are activated the GUI and front panel indicators will turn red until the values are within safe operating range.
The fault reason, day and time will be recorded in the Alarm Activation log section located at the bottom of the Alarm page.
The fault control port contact relay will be open when any alarm is activated.
7. Current Alarm Enabled Button
When this box is checked, the current alarm settings are engaged.
Select Save.
On the Status page the indicator will reflect the alarm is enabled.
8. Current Alarm Settings
Enter the value for the current alarm to trigger. The operating range is 1A–15A
Select Save.
If the alarms are activated the GUI and front panel indicators will turn red until the values are within safe operating range.
The fault reason, day and time will be recorded in the Alarm Activation log section located at the bottom of the Alarm page.
The fault control port contact relay will be open when any alarm is activated.
9. Over Voltage Alarm Settings
This feature is always enabled and cannot be disabled for the protection of your equipment.
Enter the Over Voltage trigger voltage settings. The operating range is 100V–140V.
Factory default is 132V.
Select Save.
If the alarms are activated, these indicators will turn red and all switched AC outlets will turn Off at the same time. These outlets will remain
Off and the indicator will remain red until the values are within safe operating range.
When the alarm is activated and the voltage alarm indicator is red in the GUI, the front panel OC / OV LED will also be illuminated.
The fault reason, day and time will be recorded in the Alarm Activation log section located at the bottom of the Alarm page. See fault log
information section.
10. Under Voltage Alarm Settings
This feature is always enabled and cannot be disabled for the protection of the equipment.
Enter the Under-Voltage trigger voltage settings. The operating range is 80V–120V.
Factory default is 88V.
Select Save.
If the alarms are activated these indicators will turn red and all switched AC outlets will turn Off at the same time. These outlets will remain
Off and the indicator will remain red until the values are within safe operating range.
When the alarm is activated and the Voltage Alarm indicator is red in the GUI, the front panel OC / OV LED will also be illuminated.
The fault reason, day and time will be recorded in the Alarm Activation log section located at the bottom of the Alarm page. See fault log
information section.