5. Voltage Alarm Status Indicator
• This indicator is always enabled and cannot be disabled for the protection of the equipment.
• Over Voltage (High) & Under Voltage (Low) trigger voltage settings can be set in the alarm page.
• Factory default is 132V for “HI” voltage and 88V for “LO” voltage settings.
• Voltage Alarm Recovery can be set to Auto Recover or Manual Reset. With Auto Recover, if the alarm is triggered and the AC outlets are shut
Off and the AC mains voltage is within the safe operating parameters, all outlets will turn back On automatically. If set to Manual Reset, the
AC mains need to be within the safe operating parameters and the panel power switch needs to be manually cycled.
• If the alarms are activated these indicators turn red and all switched AC outlets will turn Off at the same time. These outlets will remain Off
and the indicator will remain red until the values are within the safe operating range.
• When the alarm is activated and the Voltage Alarm indicator is red in the GUI, the front panel OC / OV LED will also be illuminated.
• The fault reason, day and time will be recorded in the Alarm Activation log section located at the bottom of the alarm page. See fault log
information section.
6. Incoming AC Mains Surge Protection Indicator
• This indicator is always enabled and cannot be disabled for the protection of the equipment.
• If an AC mains surge or spike occurs damaging the protection circuit, the incoming AC Mains Surge Protection indicator will turn from green to
red indicating the unit is damaged and needs to be repaired.
• When the alarm is activated and the AC Mains Surge Protection indicator is red in the GUI, the front panel AC fault LED will also be
illuminated. Service by a factory technician is required.
• Note: The unit may still function if the indicator is red, but all AC Mains surge protection will not function.
7. Firmware Version - Indicates the operating Firmware revision installed in the unit. Check the AtlasIED web page for the latest firmware. AP-IP
firmware can found at www.atlasied.com/ip-enabled-power-distribution. Firmware updates are done through the AP-IP discovery software.
To update the firmware, refer to Refer to the AP-IP Discovery Software Firmware Update section.