AFTER INSTALLATION CHECK
1. The screws whether have been xed effectively, and there is no risk of loosening.
2. Connector of display board whether put in the right place and do not touch the terminal board.
3. Control box cover whether cover tightly.
DIMENSION DRAWING OF OUTDOOR UNIT INSTALLATION
INSTALLATION OF OUTDOOR UNIT
Space to the obstruction
Air out side
Air in side
10 cm above
200 cm above
30 cm above
50 cm above
50 cm above
Space to the obstruction
Space to the
obstruction
Air outlet
Left installation feet
H
W2
A
D
B
W1
Right installation feet
Air inlet
Outdoor unit size oh shape
W1(W2)*H*D (mm)
A (mm) B (mm)
665(710)x420x280 430 280
600(710)x500x240 500 260
730(780)x545x285 540 280
709(761)x536x280 480 283
750(804)x550x285 480 283
800(860)x545x315 545 315
785(845)x555x300 546 316
825(880)x655x310 540 335
900(950)x700x360 632 352
970(1044)x805x395 675 410
940(1010)x1320x370 625 364
940(1008)x1366x401 610 388
650(703)x455x233 480 253
Installation outdoor unit bolt
REFRIGERATING CONNECTIONS
Use equipment and connecting pipes suitable for R32 refrigerator.
MODELS 9000 12000 18000
Min. - Max. pipe lenght with gas standard
charge (m)
3 - 5 3 - 5 3 - 5
Max. pipe lenght with gas additional charge (m) 20 20 25
Additional refrigerant charge (g/m) 15 15 25
Max. height between units (outdoor on top) (m) 10 10 15
Max. height between units (indoor on top) (m) 10 10 15
Always write the additional refrigerant charge on the data label afxed to the unit outside.