ACRC300 Series, ACRC600 Series Technical Data
(ACRC300 series only)
Primary/secondary
power feeds
The system features two power feeds. This allows a level of system fault tolerance and uninterruptible cooling.
Each feed powers 100% of the unit.
Cross circuited cooling
coil
Designed for high sensible heat ratios, the coil is constructed with copper tubes, aluminum fins, and
galvanized steel end plates.
Washable filter
(ACRC300 series only)
The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by
electrical equipment. The system uses a <20% efficiency ASHRAE 52.1, 12.7 mm (1/2 in.) washable filter that
meets HF-1 standards for electronics (MERV 1 per ASHRAE 52.2).
30% ASHRAE 52.1 filter
(ACRC600 series only)
The filtration of conditioned air is extremely vital to maintaining the clean, particle-free environment required by
electrical equipment. The system uses a 30% efficient, 102 mm (4 in), deep loading, pleated filter. Deeper
filters produce a lower pressure drop, requiring less energy during normal operation. The filter is moisture
resistant up to a 100% relative humidity. Filters are easily replaceable from the rear of the unit. (MERV 8 per
ASHRAE 52.2, EN779 G4)
Selectable top or bottom
piping connections
NOTE: Unit includes both top and bottom piping connections. Top piping connects to internal piping
connectors and routes piping upward out of the unit. Bottom piping connects to internal piping connectors
and routes piping downward out of the unit. All connections are unions for ease of installation and service.
NOTE: Top piping for ACRC300 series is available as an optional kit.
Dual float condensate
management
(Does not include
ACRC301H)
The factory-installed condensate pump is piped internally to the condensate pan. Dual floats are included with
the unit. One float is used for condensate pump control, the other to generate condensate pan overflow
alarms. For technical specifications, see Performance Data—General.
Network management Permits multi-level access to monitoring, control, and event notification features over the user’s network.
Service notifications
(ACRC300 series only)
Several components within the unit will provide a warning that service is needed. There are multiple faults that
can be detected and reported (see Alarms). Notification is also provided when a service interval expires.
Joining kit InRow RC/
NetShelter SX
Joining kits made of 16-gauge metal enable joining of the cooling system to NetShelter SX enclosures.
Remote temperature
sensor
To control the unit based on rack inlet temperature, one remote sensor is provided with ACRC300 series
(fieldinstalled) and three remote sensors are provided with ACRC600 series units (field-installed).
4.3-in. touch screen High-definition screen displays more data. Provides easytoread system status information.
Casters Allows for the unit to be moved easily.
Easy-access electrical
box
(ACRC300 series only)
Slide-out electrical box enables maintenance without removing the unit from the row.
Active Flow Controller
compatibility
Monitors pressure inside and outside the contained aisle and adjusts cooling unit fan speed to match the
airflow with that of the IT equipment.