Anybus ProfiHub B2FO2+ handleiding
Handleiding
Je bekijkt pagina 11 van 41

ProfiHub B2FO2+ User Manual| February 2018 | © PROCENTEC 10/40
The ProfiHub B2FO2+ can handle cables based on multiple protection sheaths with an overall cable diameter
between 6 to 12 mm (Fig. 8).
1.9 Cable lengths for fiber optic
The maximum cable length for fiber optic cables is 3 kilometers if G62.5 / 125 or G50/125 cable is used. If
PCF/HCS cable is used, the maximum is 200 meters.
1.10 Cable types for fiber optic
The following cable types can be used with the ProfiHub B2FO2+:
G62.5/ 125
G50 / 125
PCF/HCS
ISO / IEC 11801 (OM1)
ISO / IEC 11801 (OM2 or better)
200/230 µm (not further specified)
IEC 60793-2-10 type A1b
IEC 60793-2-10 type A1a
TIA / EIA 492AAAA
TIA / EIA 492AAAB-A
ITU-651.1
ITU-651.1
1.11 Status LEDs
The Status LEDs on the ProfiHub are very useful for diagnostics.
OFF
Blinking
ON
POWER 1 / 2
Power is not switched
on or an internal error
Power supply not
stable, redundant power
supply interrupted or an
internal failure
☺ Power supply OK
READY
Power is not switched
on or an internal error
Trying to detect the
transmission speed, but
has not locked it yet
☺ The transmission
speed has been detected
FRNC cable
Shipboard cable
Festoon cable
Flexible cable
Food cable
Robust cable
Trailing cable
Hybrid cable
Fig. 8 - Cables with different protection sheaths