Advantech LEO-S595-MS handleiding

15 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 13 van 15
www.advantech.com
13
4. Installation
3M Tapes Fix:
Tear the 3M tapes of both parts, then make sure the magnet part is placed inside the door
(portable part) and sensor is inside the door frame (fixed part). For double doors, put every part
on each door. Please clean up door surface which will stick on 3M tapes.
Screw Fix:
Remove the cover of both parts, screw the covers on the mounting positions, then install back the
devices.
Note:
1. The notch side of magnet should face the notch side of sensor, otherwise it may affect the
sensitivity of on/off detection.
2. The plane distance between sensor and magnet should not be more than 15mm, and the
height difference should be less than 7.5 mm.
5. Device Payload
All data are based on the following format(HEX):
Channel1
Type1
Data1
Channel2
Type2
Data2
Channel 3
...
1 Byte
1 Byte
N Bytes
1 Byte
1 Byte
M Bytes
1 Byte
...
5.1 Basic Information
LEO-S595-MSG0 reports basic information of sensor whenever joining the network.
Channe
Type
Description