Advantech LEO-S592-TP handleiding
Handleiding
Je bekijkt pagina 16 van 21

www.advantech.com
16
16
5. Device Payload
All data are based on the following format (HEX), the Data field should follow little-endian:
Channel1
Type1
Data1
Channel2
Type2
Data2
Channel 3
...
1 Byte
1 Byte
N Bytes
1 Byte
1 Byte
M Bytes
1 Byte
...
5.1 Basic Information
LEO-S592-TPG0 reports basic information about the sensor every time it joins the network.
Channe
l
Type
Description
ff
01(Protocol Version)
01=>V1
09 (Hardware Version)
01 40 => V1.4
0a (Software Version)
01 14 => V1.14
0b (Power On)
Device is on
0f (Device Type)
00: Class A, 01: Class B, 02: Class C
16 (Device SN)
16 digits
Example:
ff0bff ff0101 ff166732d07453450005 ff090100 ff0a0101 ff0f00
Channe
l
Type
Value
Channe
l
Type
Value
ff
0b
(Power On)
ff
(Reserved)
ff
01
(Protocol Version)
01 (V1)
Channe
l
Type
Value
Channe
l
Type
Value
ff
16
(Device SN)
6732d07453
450005
ff
09
(Hardware version)
0100
(V1.0)
Channe
l
Type
Value
Channe
l
Type
Value
Bekijk gratis de handleiding van Advantech LEO-S592-TP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Advantech |
Model | LEO-S592-TP |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 2668 MB |