Advantech LEO-S552-TP handleiding

27 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 22 van 27
www.advantech.com
22
22
(CH2)
Temperature: INT16/10, Unit: °C
Alarm Status: 00 -Alarm dismiss, 01 -Alarm
Temperature_chan
ge Alarm (CH1)
93
d7
5 Bytes, Temperature(2B) + Temperature_change(2B) +
02
Temperature: INT16/10, Unit: °C
Temperature_change: INT16/100, Unit: °C
Temperature_chan
ge Alarm (CH2)
94
d7
5 Bytes, Temperature(2B) + Temperature_change(2B) +
02
Temperature: INT16/10, Unit: °C
Temperature_change: INT16/100, Unit: °C
Example:
1. Periodic Packet
017564 0367f900 040001
Channel
Type
Value
Channel
Type
Value
01
75 (Battery)
64 => 100%
03
67 (Temperature
of Left Channel)
f9 00 => 00 f9
=>249/ 10
=24.9°C
Note: When the channel does not connect any sensor, it will report periodic packet as 030001
(CH1 no sensor) or 040001 (CH2 no sensor).
2. Temperature Threshold Alarm Packet
8367 5201 01
Channel
Type
Value
83
67
(Temperature)
52 01 => 01 52 => 338/10 = 33.8°C
01 => Temperature Threshold Alarm
3. Temperature_change Alarm Packet
94d7 4e01 c602 02
Channel
Type
Value
94
d7
Temperature: 4e 01 => 01 4e => 334/10
= 33.C
Temperature_change: c6 02 => 02 c6 =>
710/100=7.1°C
02 => Temperature_change Alarm
5.3 Downlink Commands
LEO-S552-TPG0 supports downlink commands to configure the device. The application port is
85 by default.