5.1 Basic Information
LEO-S552-TPG0 reports basic information about the sensor every time it joins the network.
Channel
Type
Description
ff
01(Protocol Version)
01=>V1
09 (Hardware Version)
01 00 => V1.0
0a (Software Version)
01 01 => V1.1
0b (Power On)
Device is on
0f (Device Type)
00: Class A, 01: Class B, 02: Class C
16 (Device SN)
16 digits
Example:
ff0bff ff0101 ff16 6723d29626820016 ff090100 ff0a0101 ff0f00
Channe
l
Type
Value
Channe
l
Type
Value
ff
0b
(Power On)
ff
(Reserved)
ff
01
(Protocol Version)
01 (V1)
Channe
l
Type
Value
Channe
l
Type
Value
ff
16
(Device SN)
6723d29626
820016
ff
09
(Hardware version)
0100 (V1.0)
Channe
l
Type
Value
Channe
l
Type
Value
ff
0a
(Software
version)
0101
(V1.1)
ff
0f
(Device Type)
00
(Class A)
5.2 Sensor Data
LEO-S552-TPG0 reports sensor data according to reporting interval (10 min by default).
Note: CH1=Left channel of LEO-S552-TPG0, CH2=Right channel of LEO-S552-TPG0.
Item
Chann
el
Type
Description
Battery Level
01
75
UINT8, Unit: %, [1-100]
Temperature (CH1)
03
67
INT16/10, Unit: °C
Temperature (CH2)
04
67
INT16/10, Unit: °C
Threshold Alarm
(CH1)
83
67
3 Bytes, Temperature(2B) + Alarm Status (1B)
Temperature: INT16/10, Unit: °C
Alarm Status: 00 -Alarm dismiss, 01 -Alarm
Threshold Alarm
84
67
3 Bytes, Temperature(2B) + Alarm Status (1B)

Bekijk gratis de handleiding van Advantech LEO-S552-TP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.