ADAM-6000/6200 RESTful User Manual
27
327
(0x0147) 0 ~ 5 V
325
(0x0145) 0 ~ 1 V
262
(0x0106) 0 ~ 500 mV
261
(0x0105) 0 ~ 150 mV
323
(0x0143) +/- 10 V
322
(0x0142) +/- 5 V
259
(0x0103) +/- 150 mV
320
(0x0140) +/- 1 V
260
(0x0104) +/- 500 mV
384
(0x0180) 4 ~ 20 mA
385
(0x0181) +/- 20 mA
386
(0x0182) 0 ~ 20 mA
If POST all, set to all channel at the same
time
Enable Low
Alarm
EnLA
Number
RW
1 / 0: Enable / Disable AI low alarm function
Only displayed when GET a single
channel
If POST all, set to all channel at the same
time
Enable High
Alarm
EnHA
Number
RW
1 / 0: Enable / Disable AI high alarm function
Only displayed when GET a single
channel
If POST all, set to all channel at the same
time
Low Alarm
Mode
LAMd
Number
RW
The alarm mode
0
Momentary
1
Latch
Only displayed when GET a single
channel
If POST all, set to all channel at the same
time
High Alarm
Mode
HAMd
Number
RW
The alarm mode
0
Momentary