Advantech ADAM-6256 handleiding
Handleiding
Je bekijkt pagina 26 van 64

ADAM-6000/6200 RESTful User Manual
26
Rng=328&
EnLA=1&
EnHA =1&
LAMd =0&
HAMd =1&
LoA=+3.25&
HiA=+15.25&
POST http://10.0.0.1/analoginput/all/config
En=0&
Rng=328&
BMd=1&
AiT=2
POST Response.
The result. If successful, the result will be "OK"; otherwise, the result will be the error
message.(refer HTTP Response Status-Code)
<ADAM-6017 status="OK">
</ADAM-6017>
➢ Resource value definitions :
Field
Abbreviation
Data Type
Property
Description
Channel
Number
ID
Number
R
0, 1, …: Analog input channel number.
Channel Enable
En
Number
RW
1 / 0: Enable / Disable AI conversion
➢ Only displayed when GET a single
channel
➢ If POST all, set to all channel at the same
time
Input Range
Rng
Number
RW
Analog input range.
Notice: Average channel is read only.
Range
code
328
(0x0148) 0 – 10 V