ADAM-5000 Series User Manual 58
ADAM-5080 Counter/Frequency Mode Selection
Users can select Bi-direction, Up/Down, Counter or Frequency options as shown
below.
Figure 6.4 Counter / Frequency Mode
Features -- Counter Mode
Up/Down Counting
The Up/Down Counter Function offers two types of counting: Up Counting (increas-
ingly) and Down Counting (decreasingly). Up Counting: when C0A+ and C0A- sense
any input signals, the counter counts up.
Down Counting: when C0B+ and C0B- sense any input signals, the counter counts
down. On receiving Up and Down signal simultaneously, the counter will not perform
each specific counting accordingly, but will remain at the previous counting value,
since these simultaneous signals won't have any effect on counting values.
Note! All four channels of ADAM-5080 will operate simultaneously in the mode
you have selected. i.e. If you switch the ADAM-5080 to Counter Mode,
all four channels will operate in Counter Mode.