Dimmer Manager software
Instruction Manual - page 29
Issue: 004
Lighting Technologies
Copying it to the other CPU - method 1
In Dimmer Manager Off-Line you make a copy of the CPU.
In the copy-of-CPU1 you change the ADN address.
You then do a SendToDimmers to CPU1 and CPU2.
Copying it to the other CPU - method 2
You do a Send To Dimmers to CPU1.
In the dimmer room on CPU2 you do a ‘Get Data Base’
On Dimmer Manager you do a ‘Get From Dimmer’ so that the PC is up to date.
Pin-out of XLR5
XLR5-M
(6117.15.110)
How to manually set Learn Values ?
Example: for CPU1 in a EURODIM 3
You set Dimmer Manager Off-line
Select the correct CPU.
Right-click > Command > Learn Loads
You get a pop-up window LearnLoads (see screenshot).
For every dimmer channel there is a pull-down selection.
One of the possible values is 600 W.