(2) Connect for a RTS (Remote Temperature Sensor) to remotely detect battery temperature,
sample distance less than 20m.
CAUTION: If the temperature sensor is short-circuited or damaged, the controller
will charge or discharge at the default temperature setting of 25 ºC.
(
3) When connect the controller to external devices, only one of the ports can be used; when
use multiple controllers in parallel, the port are for cascaded use.
(
4) Connect for RBVS (Remote Battery Voltage Sensor) to detect accurate battery voltage,
sample distance less than 20m.
(
5) Low Voltage Disconnect Voltage(V
LVD
) make the relay turn off;
Low Voltage Reconnect Voltage(V
LVR
) make the relay turn on.
(
6) Common negative design, with the same terminal of the PV and battery.
1.3 Designations of Controller Models
1.4 Accessories (Included)
Item Accessory Model Number Picture
1 Local Temperature Sensor
RT-MF58R47K3.81A
(2P-3.81mm)
1Pcs
2 Battery Voltage Sensor Terminal 2P-3.81mm
1Pcs
3
Load control delay Terminal 2P-3.81mm
1Pcs
4 Diesel generator relay Terminal 2P-3.5mm
2Pcs
WARNING: The Battery Voltage Sensor Terminal and Load Control Delay Terminal
should not mix, otherwise the controller may be damaged.