ACOPower HY-SPKP-600W50A handleiding
Handleiding
Je bekijkt pagina 16 van 36

www.acopower.com
10
Charging current (I
c
)
Discharging current (I
d
)
Start-up the Utility/Generator working:
V
BAT
<V
ON
.
Stop the Utility/Generator working:
V
BAT
<V
ON
CAUTION: The V
ON
and V
OFF
can be set via the PC software,the Battery Control
Voltage Parameters refer to the chapter 3.4 Setting.
2) Control the load first disconnection and second disconnection.
Battery Voltage (V
BAT
)
Under Voltage Warning Voltage (V
UVW
)
Under Voltage Warning Recover Voltage (V
UVWR
)
Low Voltage Disconnect Voltage(V
LVD
)
Low Voltage Reconnect Voltage(V
LVR
)
Utility/Generator Relay normally closed contact:
V
BAT
≤V
UVW
: The Utility/Generator Relay normally closed contact OFF control the load ᬚfirst
disconnection;
V
BAT
≥V
UVWR
: The Utility/Generator Relay normally closed contact ON control the loadᬚ first
connection.
Load Relay:
V
BAT
≤V
LVD
: The Load Relay OFF control the loadᬛ second disconnection;
V
BAT
≤V
LVR
: The Load Relay ON control the loadᬛ second connection;
CAUTION: The Battery Control Voltage Parameters refer to the chapter 3.4
Setting.
WARNING: When the system power off, the utility/generator relay normally
closed contact is closed, please check the system in time.