❸ Maintenance
3.1 I Wintering
• Wintering is vital to prevent the condenser breaking due to freezing. This is not covered by
the warranty.
• To avoid damaging the equipment with condensaon, do not fully cover it.
• Set the regulator to "standby" mode by pressing and holding for 3 seconds and disconnect the power supply,
• Open valve B,
• Close valves A and C and open valves D and E (if present),
• Make sure that there is no water circulang in the heat pump,
• Drain the water from the condenser (risk of freezing) by unscrewing the two water input and output connectors on
the back of the heat pump,
• In the case of full wintering for the pool (complete shutdown of the ltraon system, bleed the ltraon circuit or
even pool drainage): ghten the two connectors by one turn to prevent any foreign bodies from geng into the
condenser,
• In the case of wintering for the heat pump only (shutdown of the heang only, the ltraon keeps running): to not
ghten the connectors but add 2 caps (provided) on the condenser's water inputs and outputs.
3.2 I Maintenance
• It is recommended that the device be general serviced at least on a yearly basis to ensure
proper operaon, maintain performance levels and prevent some potenal failures. These
operaons are carried out at the user's expense, by a technician.
3.2.1 User maintenance
• Make sure that the lter is not blocked by any foreign bodies.
• Clean the evaporator (for locaon see § “5.3 I Dimensions and marking”) using a so brush and a fresh water spray
(disconnect the power cable); do not fold over the metal wings, then clean the condensaon drainage pipe to remove
any impuries that may be blocking it.
• Do not use a high pressure jet. Do not spray with rain water, salt water or water which is full of minerals.
• Clean the outside of the device; do not use any solvent-based products. We can provide you with a specic cleaning
kit as an opon: the PAC NET, see § “5.1 I Descripon”.
3.2.2 Maintenance to be carried out by a qualied technician
• Check that the regulaon is operang correctly connected.
• Check that the condensaon ows correctly when the device is operang.
• Check the safety mechanisms.
• Check the connecon of the metal masses to the earth.
• Check that the electrical cables are correctly ghtened and connected and that the electrical unit is clean.