Warming Potenal (GWP) of 675 for R32 and 2088 for R410A (European regulaon
EU 517/2014).
• In order to comply with the applicable standards and regulaons in terms of the
environment and installaon, in parcular Decree No. 2015-1790 and/or European
regulaon EU 517/2014, a leak test must be performed on the cooling circuit when
the appliance is rst started and at least once a year. This operaon must be carried
out by a specialist cered to test cooling appliances.
• The appliance must be stored in a well-venlated locaon away from all ignion
sources.
• Install the unit outdoors. Do not install the unit indoors or in an enclosed and non-
venlated outdoor locaon.
• Do not use means for accelerang the defrosng or cleaning process other than
those recommended by the manufacturer.
• The appliance must be stored in a room without any permanent ignion source
(such as open ames, operang gas appliance or operang electric heang).
• No not perforate or incinerate.
• Please note that R32 refrigerant may give o a certain odour.
INSTALLATION AND MAINTENANCE
• The appliance may not be installed close to combusble materials, or the air duct
inlet of an adjacent building.
• With some appliances, it is essenal to t a "protecon grid"-type accessory if the
unit is installed in an area with uncontrolled access.
• During installaon, troubleshoong and maintenance, pipes may not be used as
steps: the pipe could break under the weight, spilling coolant and possibly causing
serious burns.
• When servicing the appliance, the composion and state of the heat transfer uid
must be checked, as well as the absence of any traces of coolant.
• During the appliance's annual sealing test in accordance with applicable legislaon,
the high and low pressure switches must be checked to ensure that they are
securely fastened to the cooling circuit and that they cut o the electrical circuit
when tripped.
• During maintenance work, ensure there are no traces of corrosion or oil around
the cooling components.
• Before beginning work on the cooling circuit, stop the appliance and wait for a few
minutes before ng the temperature and pressure sensors. Some elements such
as the compressor and piping may reach temperatures in excess of 100 °C and high
pressures with the consequent risk of severe burns.
TROUBLESHOOTING
• All brazing must be carried out by qualied brazers.
• Replacement pipes must always be made of copper in compliance with standard
NF EN 12735-1.
• Leak detecon; pressure test:
- never use oxygen or dry air, risk of re or explosion,
- use dry nitrogen or the mixture of nitrogen and refrigerant indicated on the
informaon plate,
- the test pressure for both the high and low pressure circuits must not exceed 42
bar in cases where the appliance is equipped with the oponal pressure gauge.
• The high pressure circuit pipes are made of copper and have a diameter equal to or
greater than 1’’5/8. A cercate as indicated in §2.1 in compliance with standard
NF EN 10204 must be requested from the supplier and led in the installaon's
technical le.