H0384600.A1.EN2012/10 10
2.7Connectingtheoptions
2.7.1Hotwaterbattery

aCAE508510513
bOmega1014162028
hotwaterbattery
heatingsource
blowing
suction
Power Waterflowrate Waterloadloss Airloadloss
Primary 90/70°C 45/40°C 90/70°C 45/40°C 90/70°C 45/40°C 90/70°C 45/40°C
Unit kW m³/h mCE Pa
CAE508 23 5.9 1 1.03 1.25 1.54 30 28.5
CAE510 35 9.8 1.6 1.7 1.9 2.3 50 47.3
CAE513 41 11.6 1.9 2.01 2.5 3.12 72 67.7
Omega10 24 9.5 1.2 1.66 0.46 0.93 18 17.8
Omega14 34 11.6 1.5 2.03 0.7 1.34 30 27.9
Omega16 42 13.5 2.1 2.35 1.41 1.76 42 39.8
Omega20 53 15.2 2.35 2.64 0.51 2.17 57 53.5
Omega28 76 23 3.3 3.98 1.1 1.41 / 39.1
Powerrestitutedtotheairat27°C,enteringthehotwaterbattery.
Connectiontotheprimarycircuit:frontanyvalveorpump.
Watertemperatureinputtothehotwaterbattery:45°Cminimum,90°Cmaximum.
Maximumpressurewaterbatterycircuit:3bars.
a
b
Automaticpurge
Circulator
Checkvalveorsolenoidvalve
Shutoffvalve