REFRIGERANT NOTICE/CONCENTRATION
This air conditioner uses R32 refrigerant. The construction area for
installation, operation and storage of the air conditioner must be larger than
the minimum construction area. The minimum area for installation is
determined by:
2.Checking out in the applicable tables:
(1) For indoor unit, confirm the model of indoor unit and check the
corresponding table.
(2) For outdoor unit that is installed or placed indoors, select the
1.Refrigerant charging quantity for the entire system (ex-factory
charging quantity + additional charging quantity);
corresponding table according to the height of the room.
≥
Height of the room
<
0m
1.8m
≥2.2m
Select the applicable table
Floor standing type
Wall mounted type
Ceiling type
28