Handleiding
Je bekijkt pagina 13 van 38

Cassette Type
Check that the wiring is not broken off or disconnected.
Check that the air filter is installed.(Some air-conditioners have no air filters)
Check that the outdoor unit air outlet or inlet is not blocked.
Before you clean the air conditioner, be sure to disconnect the power supply plug.
Clean the air filter
The air filter can prevent the dust or other particulate from going inside.In case of
blockage of the filter,the working efficiency of the air conditioner may greatly decrease.
Therefore,the filter must be cleaned once two weeks during long time usage.
If the air conditioner is positioned in a dust place,the cleaning frequency of the air filter
must be increased.
If the accumulated dust is too heavy to be cleaned,please replace the filter with a new
one(replaceable air filter is an optional fitting).
1. Open the air-in grill
Push the grill switches towards the middle simultaneously as indicated in sketch A.
Then pull down the air-in grill.
The control box cables,which are originally connected with the main body electrical
terminators must be pulled off before doing as indicated below.
Caution:
2. Take out the air-in grill(together with the air filter shown in Sketch B)
Pull the air-in grill down at 45 and lift it up to take out the grill.
3. Dismantle the air filter
4.Clean the air filter(Vacuum cleaner or pure water may be used to clean the air filter.If the
dust accumulation is too heavy,please use soft brush and mild detergent to clean it and
dry out in cool place).
Checks before operation
Hanging screw bolt
Hanging bolts
Supporting
angl steele
Wooden construction
Put the square timber over the roof beam,
then install the hanging screw bolts.
Timber over the beam
Roof beam
Hanging Screw
Ceiling
New Concrete Bricks
For finished concrete bricks
Blade shape
insertion
Slide insertion
Inlaying or embedding the screw bolts.
Install the hanging hook with expansible
bolt into the concrete deep to 45~50mm
to prevent loose.
Steel bar
Embedding screw bolt
(Pipe hanging and embedding
screw bolt)
Install the supporting angle steel.
Steel roof beam structure
Bolt
Overhanging the indoor unit
Adjust the gasket (down side) to 90mm over the ceiling.
Hanging Bolt
Nut (Up Side)
Gasket (Up Side)
Installing Ear
Nut (Down Side)
Down side of the ceiling
Gasket (Down Side)
Tighten nut M10
Install the hanging bolt into T groove of the hanging tool. Overhang the indoor unit and ensure
it is level using a level indicator.
Level Indicator
Hanging Screw Bolt
Hanging Screw Bolt M10
Install it down the
installing-ear
Locking Nut M10
Hanging Ear
10 Gasket
Indoor Unit
Ceiling
Installation Plate
2
30mm
!
CAUTIONS
9
Bekijk gratis de handleiding van Yamato R32 YC18T1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Yamato |
Model | R32 YC18T1 |
Categorie | Airco |
Taal | Nederlands |
Grootte | 3862 MB |