Wascomat Junior W 75 handleiding
Handleiding
Je bekijkt pagina 13 van 59

Installation
10
1830
1838
1839
11
1137
Electrical installation
Although the machines are fitted with a thermal
overload in the motor windings a separate three-
phase common-trip circuit breaker must be
installed for all three-phase machines.
For proper overcurrent protection, check the data
plate at the rear of the machine. Also consult
local electrical code for special requirements.
Connect L1, L2, L3 and ground wires according
to the markings of the terminal block. The cable
is to hang in a large loose loop, supported by the
clip of the terminal block.
After installation, do the following:
Check the incoming power for a high voltage leg.
If present, connect that line to L2 on the terminal
block.
Start the machine and check that the drum
rotates in the proper direction during extraction,
i.e. counter-clockwise when seen from the front.
If the drum rotates in the wrong direction inter-
charge line L1 and L3 at the power connection
terminal.
Check that the transformer on the control unit is
correctly strapped in relation to the incoming
voltage. The different alternatives is printed on
the transformer circuit board.