22
System Performance
The room with the highest water temperature requirement sets the design
water temperature for the whole system based on the calculations from
the previous section.
Using the graph above it is possible to limit the specic heat output to the
required value.
The example above shows a design room air temperature of 20°C and
design heat output of 52.5W/m². Based on a 0.150 m²K/W (1.5 tog) oor
nish the oor sensor should be set to 33°C (20°C room air + 13°C ΔT) to
resulting in oor surface temperature of 25°C (20°C room air + 5°C ΔT).
Floor sensor setting for target heat output
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
0 10 20 30 40 50 60 70 8
0 90 100 110 120 130 140 150 160 170
Temperature dierence between design room air and
oor surface OR oor sensor °C
Floor sensor temperature
Floor surface temperature
Specic Heat Output, W/m²