System Performance
k
H
Value - W/m²K
Resistance
of Floor
Covering,
tog
0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00
150mm
Pipe
Centres
3.41 3.11 2.86 2.64 2.46 2.30 2.16 2.04 1.93 1.83 1.74 1.66 1.58
Using the system k
H
value to calculate the system heat output:
q = k
H
x (T
water
– T
air
)
Example:
The heat output through an 18 mm thick, ≈ 1.25 tog timber oor, over
Econna-12 with 6 mm ply, tted with pipe at 150 mm centres, in a 21°C
room heated with 40°C water is;
q = 2.30 x (40 – 21) = 2.30 x 19 = 43.7 W/m²
Alternatively, using the system k
H
value to calculate the required water
temperature, knowing the required heat output:
T
water
= ( q / k
H
) + T
air
Example:
The water temperature required to produce a heat output of 55W/m²,
through a 3 mm thick ≈ 0.25 tog LVT oor nish, over Econna-12 panels
with 6 mm ply, tted with pipe at 150 mm centres, in a 22°C room is;
T
water
= (55 / 3.11) + 22 = 18.5 + 22 ≈ 40.5°C
q = Specic Heat Output, W/m² k
H
= System Performance Factor, W/m²K
T
water
= Mean water Temperature T
air
= Room Air Temperature