System Performance
k
H
Value - W/m²K
Resistance
of Floor
Covering,
tog
0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50 2.75 3.00
Pipe
Centres
Warmup Metro - 65mm Sand & Cement Screed,
Thermal Conductivity λ = 1.20W/m
.
K
100mm 6�26 5�32 4�63 4�10 3�68 3�34 3�06 2�82 2�62 2�44 2�29 2�15 2�03
150mm
5�41 4�66 4�10 3�67 3�32 3�03 2�80 2�59 2�42 2�27 2�13 2�01 1�91
200mm 4�69 4�09 3�64 3�29 3�00 2�76 2�56 2�39 2�24 2�10 1�99 1�88 1�79
250mm 4�07 3�60 3�24 2�95 2�72 2�52 2�35 2�20 2�07 1�96 1�85 1�76 1�68
300mm
3�55 3�18 2�89 2�66 2�46 2�30 2�15 2�03 1�92 1�82 1�73 1�65 1�58
Using the system k
H
value to calculate the system heat output:
q = k
H
x ( T
water
– T
air
)
Example:
The heat output through an 18 mm thick, ≈ 1.25 tog timber oor, over
Warmup Metro, tted with pipe at 200 mm centres, in a 21°C room heated
with 40°C water is;
q = 2.76 x ( 40 – 21 ) = 2.76 x 19 = 52.44 W/m²
Alternatively, using the system k
H
value to calculate the required water
temperature, knowing the required heat output:
T
water
= ( q / k
H
) + T
air
Example:
The water temperature required to produce a heat output of 55 W/m²,
through a 3 mm thick ≈ 0.25 tog LVT oor nish, over Warmup Metro, tted
with pipe at 200 mm centres, in a 22°C room is;
T
water
= ( 55 / 4.09 ) + 22 = 13 + 22 = 35°C
q = Specic Heat Output, W/m² k
H
= System Performance Factor, W/m²K
T
water
= Mean water Temperature T
air
= Room Air Temperature