Step 1 - Electrical supply
Zoning information
In the case of bathroom installations, electrical regulations prohibit the
installation of mains voltage products such as thermostats, contactors,
fused spurs, isolators or junction boxes, within Zones 0 or 1.
Any mains voltage product tted within Zone 2 must have a degree of
protection at least of IPX4 or IPX5 if water jets are present.
It is common to install the thermostat outside of wet rooms in the adjacent
connected room in circumstances where it is not practical to install the
thermostat within the wet room.
When installed in this way, using only the sensor to control the heating,
it is not possible to directly control the air temperature, only the surface
temperature�
All electrical connections must conform to the current BS 7671
National Wiring Regulations. Final connections to the main
electricity supply MUST be completed by a Part P qualied
electrician.
ZONE 0
ZONE 2
ZONE 1
ZON
E 2
Z
O
N
E
2
Z
ON
E
2
ZO
N
E 0
Z
O
N
E 1
2.2
5
m
2.
2
5
m
0
.
6
m
0
.
6
m
0
.
6
m
0
.
6m
0.
6
m
0.
6m
0.
6m

Bekijk gratis de handleiding van Warmup Foil Heater, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkWarmup
ModelFoil Heater
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11009 MB